Feature and Benefits
Technical Specification
| Approvals | LPCB / CE-CPR | 
| Operating Voltage | 20 V to 28 V DC | 
| Current Parameters | Standby:23mA Commission:56mA Alarm:33mA | 
| Beam Sensor Sensitivity | Level 1: 2.6 dB High Sensitivity | 
| Level 2: 3.8 dB Medium Sensitivity | |
| Level 3: 5.8 dB Low Sensitivity | |
| Beam Pathway Length | Span 1: 8 to 20 meters Short Path (1x mirror reflector required) | 
| Span 2: 20 to 40 meters Short Path (1x mirror reflector required) | |
| Span 3: 40 to 70 meters Normal Path (4x mirror reflector required) | |
| Span 4: 70 to 100 meters Long Path (4x mirror reflector required) | |
| Beam Path Angle | ± 0.4O Directional | 
| Alignment Guide | Laser Beam Pointer | 
| Digital Display Guide | Nixie Tube | 
| LED Indicator Guide | Red: Fire; Yellow: Fault; Green: Alignment | 
| Reset Time | Less than 2 Second (Power Cut) | 
| Relay Capacity [Fire/Fault] | Normally Open/ 2.0 A; 30 VDC | 
| Material / Colour | ABS / White | 
| Dimension / Weight | L:190.87 x W:126.87 x H:91.96 mm / 440 gm | 
| Weight | 0.130 Kg with base | 
| Accessories | Mounting Bracket, 4 x Mirror Reflector | 
| Operating Temperature | -10°C to 55°C | 
| Protection Rating | IP30 [IP66 glue seal-For permanent fixing] Indoor Application | 
| Humidity | 0 to 95% RH, Non condensing |